Image for Illustration purposes only. Actual product may vary
ABB
MS116-1.6-1SAM250000R1006 Manual Motor Starter
ABB MS116-1.6-1SAM250000R1006 Manual Motor StarterMODEL MS116-1.6-1SAM250000R1006
Call for Pricing - 888-671-2883
Typically Ships in: 1 day
Returnable: Yes
ABS certificate
1SAA963000-0103
Actuator type
Rotary Handle
Ambient air temperature compensation
Yes
Ampere rating UL/CSA
16 A
BV certificate
1SAA963000-0202
CB certificate
1SAA963000-2002
CCC certificate
1SAA963000-3803
Connecting capacity main circuit UL/CSA
Flexible 1/2x 16-8 AWG Stranded 1/2x 16-8 AWG
Contact position indication
ON / OFF
Conventional free-air thermal current (Ith)
Main Circuit 16 A
cUL certificate
cUL_E137861
Data sheet, technical information
2CDC131025D0201
Data sheet, technical information (Part 2)
1SAM200505F0011
Data sheet, technical information (Part 3)
1SAM200507F0001 1SAM200507F0002 1SAM200507F0003 1SAM200508F0001 1SAM200508F0002 1SAM200508F0003
Declaration of conformity - CE
1SAD938516-0060
Degree of protection
IP20
DNV certificate
1SAA963000-0302
eClass
7.0 27370401
Electrical durability
100000 cycle
ETIM 4
EC000074 - Motor protective circuit-breaker
ETIM 5
EC000074 - Motor protective circuit-breaker
ETIM 6
EC000074 - Motor protection circuit-breaker
General use rating UL/CSA
(600 V AC) 16 A
GL certificate
1SAA963000-0402
GOST certificate
1SAA937000-2703
LR certificate
1SAA963000-0505
Max operating altitude permissible
2000 m
Maximum operating voltage UL/CSA
Main Circuit 600 V AC
Mechanical durability
100000 cycle
Mounting position
Position 1 to 6
Number of poles
3
Object classification code
F
Operational current
1.6 A
Operational voltage
690 V AC
Poles
3
Pollution degree
3
Rated frequency
Main Circuit 50 Hz Main Circuit 60 Hz
Rated impulse withstand voltage (U imp)
Main Circuit 6 kV
Rated instantaneous short-circuit current setting (Ii)
240 A
Rated insulation voltage (Ui)
690 V
Rated operational current (Ie)
16 A
Rated operational current AC-3 (Ie)
16 A
Rated operational power AC-3 (Pe)
(400 V) Three Phase 7.5 kW
Rated operational voltage
Main Circuit 690 V AC
Rated service short-circuit breaking capacity (Ics)
(230 V AC) 16 kA (400 V AC) 16 kA (440 V AC) 4 kA (500 V AC) 4 kA (690 V AC) 2 kA
Rated ultimate short-circuit breaking capacity (Icu)
(230 V AC) 16 kA (400 V AC) 16 kA (440 V AC) 4 kA (500 V AC) 4 kA (690 V AC) 2 kA
Recommended screw driver
Pozidriv 2
Resistance to shock acc. to IEC 60068-2-27
11 ms Pulse 25g
Resistance to vibrations acc. to IEC 60068-2-6
5g / 3 ... 150 Hz
RMRS certificate
1SAA918000-0703
RoHS information
1SAA963001-4407
RoHS status
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Setting range
10 ... 16 A
Tightening torque
Main Circuit 0.8 ... 1.2 Nm
Tightening torque UL/CSA
Main Circuit 10 inlb
UL certificate
UL_E137861
Wire stripping length
Main Circuit 9 mm
Ambient air temperature: Around the Enclosure 0 ... +40 C Operation -25 ... +70 C Operation Compensated -25 ... +55 C Storage -50 ... +80 C
Connecting capacity main circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm Flexible 1/2x 0.75 ... 2.5 mm Rigid 1/2x 1 ... 4 mm
Horsepower rating UL/CSA: (220 ... 240 V AC) Three Phase 5 Hp (440 ... 480 V AC) Three Phase 10 Hp (550 ... 600 V AC) Three Phase 10 Hp
Mounting on DIN rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
When you get to checkout, you’ll be able to select a free gift! Depending on the cart value, you’ll be shown relevant gifts your order qualifies for.
$500
MRO Hat
MRO Golf Balls
MRO Hi-Vis Vests
MRO Mug
$750
32oz Water Bottle
Throw Blanket
30 piece Hex Set
Telescopic Pick Up
$1,250
Golf Cooler
11-in-1 Screw Driver Set
Gorilla Grip Knee Pad
John Deere Oilskin Hat
$2,500
Igloo 1/2 Gallon Jug
Rechargable Headlamp
Larix Trucker Hat
$5,000
Igloo 10 Gallon Cooler
Igloo Party Bucket Cooler
Klein Tools Speaker
Klein Tools 8-in-1
$7,500
GX-6F Pro Golf Range Finder
Bushnell Outdoorsman Speaker
Jaeger 24px Ratcheting Wrench Set
Aspen Beverage Bucket